10KW-40KW Modular type water cooled water chiller & heat pump

Short Description:

Advantages: Mini type cooling / heating capacity 10~35kw, modular type:100-400Kw. Adopt Copland Scroll type compressor and famous main components to ensure high efficiency operation, mini type COP can reach 6.16. High quality tube in tube heat exchanger, anti-block,anti-freeze. Built-in four way valve, internal switch, to simplify users’ water system. Built-in water pump, Constant pressure device, easy to install. R410A earth friendly refrigerant. Start and alarm by mobile message. &...


  • FOB Price: US $0.5 - 9,999 / Piece
  • Min.Order Quantity: 100 Piece/Pieces
  • Supply Ability: 10000 Piece/Pieces per Month
  • Compressor type: scroll type
  • Evaporator Type: tube in tube heat exchanger
  • Standard pressure-bearing: 1 MP
  • Dimension: 1100mm*600mm*1310mm
  • Net weight: 180kg-320kg
  • Opearting weight: 24kg-430kg
  • Product Detail

    video

    Product Tags

    Advantages:

    Mini type cooling / heating capacity 1035kw, modular type:100-400Kw.
    Adopt Copland Scroll type compressor and famous main components

    to ensure high efficiency operation, mini type COP can reach 6.16.
    High quality tube in tube heat exchanger, anti-block,anti-freeze.

    Built-in four way valve, internal switch, to simplify users’ water system.
    Built-in water pump, Constant pressure device, easy to install.

    R410A earth friendly refrigerant.

    Start and alarm by mobile message.

     

    Optional Accessories:

    Danfoss plate exchanger,

    Sanyo/Dakin compressor

    R410A, R407C.

    Heat recovery

    Rubber absorber

    Metallic filter for the water circuit

    Water pump

    Water flow switch

     

    Nomenclature

     

    SM 020— WD

     

    Built in water pump

     

    Technical specification  underground type

    Model

    SM10-HY

    SM15-HY

    SM20-HY

    SM-25HY

    SM-30HY

    SM40-HY

    Cooling capacity

    kW

    10

    15

    20

    25

    30

    40

    Heating capacity

    kW

    12

    16

    24

    28

    32

    45

    Power input

    Cooling

    kW

    2.26

    2.9

    4.52

    5.5

    5.8

    6.7

    Heating

    kW

    3.11

    4.0

    6.22

    6.8

    8

    8.6

    Compressor type

    scroll type

    Refrigerant Type

    R407c/R410a

    Power supply

    V/Ph/Hz

    380/3/50

    Safety protection

     high/low pressure protection, over load protection, phase protection, waterflow switch protection, exhaust air temp. protection, Over high/low outlet water temp. protection, anti-freezing protection

    Evaporator

    Type

    tube in tube heat exchanger

    Water side resistance

    kPa

    60

    Waterflow in heating

    m3/h

    1.7

    2

    2.6

    3.4

    4

    5.2

    Pipe connection

    DN25

    DN40

    Standard pressure-bearing

    MPa

    1

    Condenser

    Type

    tube in tube heat exchanger

    Water side resistance

    kPa

    60

    Waterflow in cooling

    m3/h

    2

    2.5

    3.1

    4

    5

    6.2

    Pipe connection

    DN25

    DN40

    Standard pressure-bearing

    MPa

    1

    Dimension

    Length

    mm

    1100

    Width

    mm

    600

    Height

    mm

    1310

    Net weight

    kg

    180

    200

    220

    240

    280

    320

    Opearting weight

    kg

    240

    270

    300

    330

    380

    430

     

    1.Cooling Condition:Chilled water (User Side) in/out 12/7℃; Cooling water (Source Side) in/out 25/30℃.

    2.Heating Condition:Hot water (User Side) in/out 40/45℃; Cooling water (Source Side) in/out 4/8℃.

    Underwater type

    Model

    SM10-HY

    SM15-HY

    SM20-HY

    SM-30HY

    SM40-HY

    Cooling capacity

    kW

    10

    15

    20

    30

    40

    Heating capacity

    kW

    12

    16

    24

    32

    45

    Power input

    Cooling

    kW

    1.8

    2.8

    3.7

    5.5

    7.5

    Heating

    kW

    2.5

    3.5

    5.0

    6.0

    8.8

    Compressor type

    scroll type

    Refrigerant Type

    R410a or R22

    Power supply

    V/Ph/Hz

    380/3/50 or 220/50

    380/3/50

    380/3/50 or 220/50

    380/3/50

    Safety protection

     high/low pressure protection, over load protection, phase protection, waterflow switch protection, exhaust air temp. protection, Over high/low outlet water temp. protection, anti-freezing protection

    Evaporator

    Type

    tube in tube heat exchanger

    Water side resistance

    kPa

    60

    Cold Water flow in cooling

    m3/h

    1.7

    2.6

    3.4

    5.2

    6.9

    Pipe connection

    DN25

    DN40

    Standard pressure-bearing

    MPa

    1

    Condenser

    Type

    tube in tube heat exchanger

    Water side resistance

    kPa

    60

    Cooling water flow in cooling

    m3/h

    2.2

    3.2

    4.3

    6.5

    8.6

    Pipe connection

    DN25

    DN40

    Standard pressure-bearing

    MPa

    1

    Dimension

    Length

    mm

    880

    Width

    mm

    660

    Height

    mm

    1380

    Net weight

    kg

    180

    200

    220

    280

    320

    Opearting gweight

    kg

    240

    270

    300

    330

    380

    430

     

    1.Cooling Condition:Chilled water (User Side) in/out 12/7℃; Cooling water (Source Side) in/out 18/29℃.

    Heating Condition:Hot water (User Side) in/out 40/45℃; Cooling water (Source Side) in/out 15/7℃.

        Model

    SM100

    SM150

    SM200

    SM250

    SM300

    SM400

    Cooling capacity ( kW)

    90

    135

    180

    225

    270

    360

    Heating capacity( kW)

    100

    150

    200

    250

    300

    400

    Power input

    Cooling  kW

    15.0

    22.5

    30.0

    37.5

    45.0

    62.0

    Heating kW

    20.4

    30.6

    40.8

    51

    61.2

    84.0

    Compressor type

    Scroll

    Screw

    Refrigerant Type

    R407C/R410A

    Power supply

    V/Ph/Hz

    380V/50Hz/3P

    Safety protection

     high/low pressure protection, over load protection, phase protection, waterflow switch protection, exhaust air temp. protection, Over high/low outlet water temp. protection, anti-freezing protection

    Evaporator

    Type

    Shell in tube

    Water side resistance (kPa)

    55

    55

    55

    55

    55

    55

    Waterflow in heating(m3/h)

    8.6

    12.9

    17.2

    21.5

    25.8

    34.0

    Pipe connection

    DN65

    DN65

    DN65

    DN65

    DN80

    DN100

    Condenser

    Type

    Shell in tube

    Water side resistance (kPa)

    60

    60

    60

    60

    60

    60

    Waterflow in cooling(m3/h)

    8

    12

    16

    21

    25

    33

    Pipe connection

    DN65

    DN65

    DN65

    DN65

    DN80

    DN100

    Dim

    L(mm

    1600

    2000

    2000

    2000

    2300

    2400

    W(mm

    800

    800

    800

    800

    800

    840

    H(mm

    1600

    1600

    1600

    1700

    1700

    1850

    Unit weight(Kg

    Shipping weight

    590

    900

    1050

    1380

    1580

    2200

    Opearting weight

    820

    1140

    1360

    1680

    2100

    2600

    1.Cooling Condition:Chilled water (User Side) in/out 12/7℃; Cooling water (Source Side) in/out 18/29℃.

    3.Heating Condition:Hot water (User Side) in/out 40/45℃; Cooling water (Source Side) in/out 15/7℃.

    Dimension:

    Mini type:

     

    Model SM-10HY SM-15HY SM-20HY SM-25HY SM-30HY SM-40HY

    a

    DN25

    DN40

    b

    DN25

    DN40

    c

    DN25

    DN40

    d

    DN25

    DN40

     

    Modular type:

     

    Capacity in different condition

     

    Standard Electrical wire:

     

    Unit Model

    Wire specification

    SM10-HY

    3*4mm2+2*15mm2

    SM15-HY

    3*4mm2+2*15mm2

    SM20-HY

    3*4mm2+2*15mm2

    SM25-HY

    3*4mm2+2*15mm2

    SM30-HY

    3*4mm2+2*15mm2

    SM40-HY

    3*4mm2+2*15mm2

     

    Installation and Maintenance

    Installation

    1. Please check the units carefully referring to packing list after the units are transported to installation site.

    Please inform the sales department if there is any damage to the unit in transportation.

    1. Customers supply ametabolic rigid foundation or concrete foundation, the size of foundation refers to the size of four orientation hotels of unit, the foundation can adopt frame structure, with the frame on girder or pole, ensure that frame can support 150% times of unit weight and a solid level foundation.
    2. Installation site:

    The unit can be installed on the ground indoor or outdoor. Please note the following factors:

    (1) The site is horizontal and can support 1.5 times’ weight of the unit.

    (2) Ensure enough space around and above the unit for maintenance.

    (3) Leave barrel-drain around the unit to discharge water for seasonal shut down.

    Standard of underground water

    1. To ensure the heating capacity in winter according to the variable temperature of underground water, we need revise the water flow.

    (1) When the temperature is too low, increase the water flow.

    (2) In cooling condition, when the temperature is too high, increase the water flow.

    1. Check the revise coefficient according to the diagram below.
    2. The actual water flow is the standard water flow multiply by the revised coefficient.
    3. When the underground water flow is uncertain, select the unit model according to the cooling or heating capacity first, then calculate the water flow according to the unit’s technical sheet and the temperature of underground water. Then work out the mining plan of the underground water.
    4. Beside the temperature and water flow of the underground water, users need also provide a report about the corrosion of the underground water to copper, iron and other metals.
    5. If the temperature of the underground water in not included in the sheet, please call the Technical Service Department.

    Water Quality Standard

     

    Item

    Evaporator side water

    Condenser side water

    PH

    6.5—8.5

    6.0—8.0

    electric conductivity

    ≤200uv/cm25℃

    ≤200uv/cm25℃

    chlorde ion

    ≤50ppm

    ≤200ppm

    sulfate ion

    ≤50ppm

    ≤200ppm

    Total iron content

    ≤0.3ppm

    ≤0.5ppm

    alkali ion

    ≤50ppm

    ≤100ppm

     total hardness

    ≤50ppm

    ≤100ppm

    sulfidion

    NO

    NO

    ammonium ion.

    NO

    NO

    sandd

    ≤30ppm

    ≤50ppm

     sodion

    No requirement

    No requirement

     

    Power Supply

     

    1. The wire and connection should obey the standard.
    2. The ground wire should be connected well to the ground.
    3. Ensure the phase sequence is right.

     

    Maintenance

     

    1. Units should be managed, maintained by professional person. If abnormal situation is observed, stop units at once and find the reason. The deal with the units. Units can not run with illness.

    2. Maintenance the unit correctly and regularly. The cooling and cold water need to be discharged if the unit is not available for a long time to prevent the ice broke the pipe.

     

    Note

    1. If the water temperature is lower than or near to 0, users need to add antifreeze in coled water.
    2. Clean the water system regularly.